Plate Heat Exchanger Components
A plate heat exchanger consists of a strong frame that holds a pack of thin, corrugated plates tightly together. Each component plays a role in the performance, reliability and serviceability of the heat exchanger.
On this page, we go through the main components of a traditional SonFlow plate heat exchanger and explain how each one is designed.
Main Components at a Glance:
- Head
- Follower
- Carrying Bar
- Guiding Bar
- Column
- Plate Pack
- Tie Bolt
- Connections
- Foundation Feet
Frame
The frame forms the foundation of any plate heat exchanger, so it is important that it is strong, rigid and durable.
SonFlow frames comply with applicable legislation and international standards. By default, our frames are designed in accordance with the PED 2014/68/EU (EN 13445) and ASME Section VIII, Div. 1 construction standards.
Our frames are painted in a durable RAL 5010 blue, and other colours are available on request. We also offer different paint systems according to our customers’ specifications, as different systems are suited to different conditions – such as the installation environment or the media itself.
Furthermore, our frames are designed to make assembly, servicing and maintenance as easy as possible.
Follower
The follower is fitted with a large roller, so it can easily slide back and forth. This makes opening and closing the plate heat exchanger a straightforward task when service and maintenance are required.
Optional Features
Inspection holes can be fitted to allow easy examination of the plate pack. This is particularly useful when handling media containing pulp or fibres, which tend to cause fouling in the heat exchanger.
Seawater filters can also be fitted to the plate heat exchanger. This is particularly relevant in the marine and offshore industry, aboard vessels or platforms. The filter catches smaller particles, resulting in longer intervals between service and maintenance.
Tie Bolts
SonFlow tie bolts are designed to be tightened from the head side of the plate heat exchanger. This makes opening, closing and tightening the heat exchanger easier, as the ratchet spanner does not need to be moved along the entire length of each tie bolt. This significantly reduces labour effort and assembly time.
Head
By default, we design our plate heat exchangers as single-pass solutions with all connections on the head.
Having all connections on the head makes service and maintenance very easy, as there is no need to dismantle the pipework to access the interior of the heat exchanger.
The head and the column can be fitted with sturdy foundation feet, making it easy to secure the heat exchanger to the rest of the installation.
Plate Pack
The heart of the plate heat exchanger is the plate pack, where heat transfer takes place. The plate pack consists of a number of plates developed for high heat transfer and a long service life.
The combination of plate type and pattern determines the efficiency of the heat exchanger and is calculated to match the thermal requirements of the duty.
Each plate is fitted with a high-quality gasket that seals the heat exchanger, guides the flow and aligns the plates.
Connections
SonFlow traditional plate heat exchangers have connections from DN 25 to DN 500 – both threaded and flanged – designed to the most widely used standards. This eliminates the need for reducers in the piping system.
Our flange connections can be rubber-lined or clad in the same material as the plates, such as AISI 316 or titanium, to protect against corrosion damage.
Connection sizes are matched to the duty, so the flow velocity does not change at the transition between the pipework and the heat exchanger. This reduces wear on the pipe installation, resulting in lower maintenance costs and more stable operation.
Carrying Bar
Our carrying bars are designed to be strong enough to prevent distortion or sagging from the weight of the plate pack – even after many years of operation.
The carrying bar also allows the plates to slide along it easily. The bar is long enough to clean the plates without removing them from the frame, saving time and money during service.
Additionally, the carrying bar is designed so that a single plate can be removed without having to remove all the other plates.
Guiding Bar
The guiding bar is a very important part of the frame that is often overlooked when designing a heat exchanger. It prevents misalignment, or “snaking”, of the plate pack by supporting the plates during assembly and when the heat exchanger is opened for service.
The bar must be strong enough to withstand the side load from the powerful tightening forces exerted when the heat exchanger is assembled.
Technical Specifications
Design pressure:
- Painted frames: 0.6/1.0/1.6/2.5/3.0 MPa (87/145/232/362/435 PSI)
- Other design pressures available on request
Construction standards:
- PED 2014/68/EU (EN13445)
- ASME Section VIII, Div. 1
Performance certificate:
- AHRI (LLHE)
Frame:
- Painted frame, RAL 5010 (available in other colours)
- Some models can be delivered with a stainless steel frame
Connections:
- From DN25 up to DN500 flanges in carbon steel,
rubber-lined, or clad with AISI 316 or titanium - Designed to the most widely used standards
Plate material:
- AISI 304/316 and titanium
- Other materials available on request
Gasket materials:
- Nitrile, EPDM and Viton
- Other materials available on request
Accessories:
- Safety cover in stainless steel
- Insulating jacket
- Assembly spanner
- Foundation feet
- Instrument flange
- Thermometer and manometer
- Drip tray